Protection and Automation Functions
7.24 Instantaneous Tripping at Switch onto Fault
Normally, the pickups of protection functions and stages with high fault current are selected:
Overcurrent protection (phase and ground)
A specific protection stage is generally used. This can be one of the protection stages provided for the protec-
tion application, which itself trips with a delay. An additional protection stage with settings optimized for this
use case, for example, increased threshold value and blocking of self-tripping, can also be used.
Parameter: Operate delay
Recommended setting value (_:5941:6) Operate delay = 0.00 s
When switching onto a fault, the tripping should usually be instantaneous. The tripping delay is therefore set
to 0.
7.24.5

Settings

Addr.
Stage 1
_:5941:1
_:5941:2
_:5941:6
_:5941:102

Information List

7.24.6
No.
Group indicat.
_:4501:55
_:4501:57
Stage 1
_:5941:81
_:5941:54
_:5941:52
_:5941:53
_:5941:55
_:5941:57
870
Parameter
Stage 1:Mode
Stage 1:Operate & flt.rec.
blocked
Stage 1:Operate delay
Stage 1:Configuration
Information
Group indicat.:Pickup
Group indicat.:Operate
Stage 1:>Block stage
Stage 1:Inactive
Stage 1:Behavior
Stage 1:Health
Stage 1:Pickup
Stage 1:Operate
C
Setting Options
off
on
test
no
yes
0.00 s to 60.00 s
Setting options depend on config-
uration
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Default Setting
off
no
0.00 s
Data Class
Type
(Type)
ACD
O
ACT
O
SPS
I
SPS
O
ENS
O
ENS
O
ACD
O
ACT
O