Application And Setting Notes - Siemens 6MD85 Manual

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

7.21.4.2

Application and Setting Notes

Parameter: Threshold
Default setting (_:13231:3) Threshold = 3.000 Hz/s
The pickup value depends on the application and is determined by power-system conditions. In most cases, a
network analysis will be necessary. A sudden disconnection of loads leads to a surplus of active power. The
frequency rises and causes a positive frequency change. On the other hand, a failure of generators leads to a
deficit of active power. The frequency drops and results in a negative frequency change.
The following relations can be used as an example for estimation. They apply for the change rate at the begin-
ning of a frequency change (approximate 1 s).
Where:
f
rated
ΔP
S
rated
H
Typical data for H:
For hydro generators (salient-pole machines)
For turbine-driven generators (non-salient pole rotors)
For industrial turbine-driven generators
EXAMPLE
f
= 50 Hz
rated
H = 3 s
Case 1: ΔP/S
rated
Case 2: ΔP/S
rated
Case 1: df/dt = -1 Hz/s
Case 2: df/dt = -4 Hz/s
Parameter: Operate delay
Default setting (_:13231:6) Operate delay = 1.00 s
You can use the Operate delay parameter to avoid overfunction due to disturbing influences (for example,
switching operations). If the protection function is supposed to respond quickly, set the Operate delay
parameter to 0 s.
For monitoring small changes (< 1 Hz/s), a small time delay is useful to avoid overfunctioning.
Parameter: Dropout differential
Recommended setting value (_:13231:4) Dropout differential = 0.10 Hz/s
You can use the Dropout differential parameter to define the dropout value. The recommended value
is 0.10 Hz/s.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Rated frequency
Active power change
ΔP = P
- P
Consumption
Generation
Rated apparent power of the machines
Inertia constant
= 0.12
= 0.48
Protection and Automation Functions
7.21 Rate of Frequency Change Protection
H = 1.5 s to 6 s
H = 2 s to 10 s
H = 3 s to 4 s
849