Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
By routing the Trip/open cmd. 3-pole signals to 1 or 2 binary outputs, you can carry out 1, 1.5, and 2-
pole activations of the circuit breaker. You can find a detailed description of this in chapter
Variants of the Circuit
NOTE
i
i
Do not confuse these 1-pole, 1.5-pole, and 2-pole activations of the circuit breaker with 1-pole or 3-pole
tripping of the circuit breaker.
Routing for Analysis of the Circuit-Breaker Switch Position
For certain functions of the device, it is useful to detect the circuit-breaker switch position via its auxiliary
contacts. These are for example:
Circuit-breaker position recognition function block
Circuit-breaker failure protection function
Control function block
The operating principle of the auxiliary contacts is described in the individual functions.
Depending on the application, Siemens recommends the following different interfaces for the auxiliary
contacts:
The device performs protection and automatic reclosing functions without any control functionality.
For optimal performance of the protection and automatic reclosing functions, the Pole closed informa-
tion should be acquired selectively via the auxiliary contacts.
[loauswer-081210-01.tif, 1, en_US]
Figure 5-44
Make the routing to the binary input as G_ (closed). In the following figure, routing is executed as CH, in
which H stands for active with voltage.
[scpolges-081210-01.tif, 1, en_US]
Figure 5-45
242
Breaker.
Recommended Analysis of the Circuit-Breaker Switch Position when Used as a Protection
Device
Pole Closed: Routing for the Acquisition of Pole Closed Information
6.2.2.3 Connection
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017