Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

[LoCBWIxF, 1, en_US]
Figure 9-25
(1)
Current-flow criterion fulfilled
(2)
20 ms prior value
Calculation of the Wear
If the ΣI
x
-method stage receives the logic release signal, the determined tripping current is used in the calcula-
tion of wear. The calculation results are then added to the existing statistic values of the ΣI
follows, with phase A as example.
[FoCBWIxA-301012-01.tif, 1, en_US]
Where:
x
q
m
The phase-selective ΣI
the specific application.
To simplify the interpretation of the sum of the tripping current powers, the values are set in relation to the
exponentiated rated normal current I
Circuit-Breaker Maintenance Warning
If the summated ΣI
generated.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Logic of the Determination of the Tripping Current Value
Parameter exponent
No. of circuit-breaker switching cycle
Tripping/opening current of phase A to the power of x in the qth circuit-
breaker operation
Rated normal current to the power of x
Statistic value of current phase A calculated with the ∑I
Total number of switching cycles
x
value is available as statistical value. You can reset or preset the statistics according to
of the circuit-breaker (see also Setting notes).
rated
x
value of any phase is greater than the threshold, a phase-selective warning signal is
Measured Values, Energy Values, and Supervision of the Primary System
9.6 Circuit-Breaker Wear Monitoring
x
method as
x
method
1025