Protection and Automation Functions
7.11 Instantaneous High-Current Tripping
The maximum 3-phase short-circuit current I"
[foglchik-170309-01.tif, 1, en_US]
With a safety margin of 10 %, the following setting value results:
[foglnste-170309-01.tif, 1, en_US]
If short-circuit currents exceed 1496 A (primary) or 12.5 A (secondary), there is a short circuit on the line to be
protected. It can be disconnected immediately.
NOTE
i
i
The calculation was performed with absolute values, which is accurate enough for overhead lines. A
complex calculation is required only if the source impedance and the line impedance have extremely
different angles.
Parameter: Dropout ratio
Recommended setting value (_:3901:4) Dropout ratio = 0.90
The recommended setting value of 0.90 is sufficient for many applications. To obtain high-precision measure-
ments, the Dropout ratio can be reduced. If you expect highly fluctuating measurands at the pickup
threshold, you can increase the setting value of the parameter Dropout ratio. This avoids chattering of the
tripping stage.

Release Procedure via Protection Interface

7.11.5
This stage can be applied only if the device is equipped with a protection interface.
770
flowing through is (at a source voltage of 1.1 V
sc
SIPROTEC 5, High-Voltage Bay Controller, Manual
):
N
C53000-G5040-C015-9, Edition 11.2017