Measured Values, Energy Values, and Supervision of the Primary System
9.6 Circuit-Breaker Wear Monitoring
ΣI*-Method Stage
9.6.4
9.6.4.1

Description

Logic of the Stage
[LoCBWIxS, 3, en_US]
Figure 9-24
Determination of the Tripping/Opening Current Value
RMS values of the fundamental components are stored for each phase in a buffer during the time between the
start criterion and the pole-opening-starts criterion. With the coming pole-opening-starts criterion, the latest
value in the buffer is searched for whose value is above the setting of parameter Current thresh. CB
open. The 20 ms prior value is used as tripping/opening current for further calculation.
If no value within the buffer is above the setting value, this circuit-breaker opening affects only the mechan-
ical lifetime of the circuit breaker and is consequently not considered by this method.
1024
Logic of the ΣI
x
-Method Stage
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017