System Functions
3.5 Protection Communication
[scbauszw-021210-01.tif, 1, en_US]
Figure 3-65
3.5.2.8
Diagnostic Measured Values of the Protection Interface
The following diagnostic data is provided via the protection interfaces by the devices in the constellation:
•
Address of the device in the constellation
•
Circuit-breaker switch position (open/closed/undefined) (only for protection interfaces of type 1)
•
Availability of protection-interface communication within the last minute, as percentage
Availability of protection-interface communication within the last hour, as percentage
•
Time delay in the send and receive direction of the telegrams between local and neighboring device
You can find this diagnostic data in DIGSI under the following menu structure (see
[sc_diagnose_wskanäle_geräteadresse, 2, en_US]
Figure 3-66
118
Routing of Metered Values to the Protection Interface in Device 2
Protection-Interface Channel Diagnostic Data – Device Address
Figure
3-66):
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017