Settings - Siemens 6MD85 Manual

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Set the time value in seconds. The characteristic curve is displaced using the Time dial parameter.
NOTE
i
i
The value pairs must be entered in continuous order.
7.6.6.3

Settings

Addr.
General
_:1
_:2
_:110
_:8
_:112
_:109
_:111
_:10
_:26
_:27
_:3
_:115
_:101
Dyn.s: AR off/n.rdy
_:28
_:35
Dyn.set: AR cycle 1
_:29
_:36
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
C
User curve #:Mode
User curve #:Operate &
flt.rec. blocked
User curve #:Directional
mode
User curve #:Method of
measurement
User curve #:Non-direc-
tional pickup
User curve #:Directional
comparison
User curve #:Release via
input signal
User curve #:Blk. by
meas.-volt. failure
User curve #:Dynamic
settings
User curve #:Blk. w.
inrush curr. detect.
User curve #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
5 A @ 100 Irated 0.150 A to 175.000 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
User curve #:Reset
User curve #:Time dial
User curve #:Effect. by
AR off/n.ready
User curve #:Stage
blocked
User curve #:Effected by
AR cycle 1
User curve #:Stage
blocked
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
Setting Options
off
on
test
no
yes
forward
reverse
fundamental comp.
RMS value
no
at volt.< & mem.empty
no
yes
no
yes
no
yes
no
yes
no
yes
0.030 A to 35.000 A
0.150 A to 175.000 A
0.001 A to 1.600 A
0.005 A to 8.000 A
instantaneous
disk emulation
0.05 to 15.00
no
yes
no
yes
no
yes
no
yes
Default Setting
off
no
forward
fundamental
comp.
at volt.< &
mem.empty
no
no
yes
no
no
1.500 A
7.500 A
1.500 A
7.500 A
1.500 A
7.500 A
disk emulation
1.00
no
no
no
no
691