Addr.
_:2311:9
General
_:781:1
_:781:2
_:781:26
_:781:27
_:781:8
_:781:3
_:781:108
_:781:113
_:781:109
_:781:101
_:781:115
Dyn.s: AR off/n.rdy
_:781:28
_:781:35
Dyn.set: AR cycle 1
_:781:29
_:781:36
_:781:14
_:781:102
Dyn.set: AR cycle 2
_:781:30
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
C
General:Measured value
Inverse-T 1:Mode
Inverse-T 1:Operate &
flt.rec. blocked
Inverse-T 1:Dynamic
settings
Inverse-T 1:Blk. w. inrush
curr. detect.
Inverse-T 1:Method of
measurement
Inverse-T 1:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
5 A @ 100 Irated 0.05 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Inverse-T 1:Type of char-
acter. curve
Inverse-T 1:Min. time of
the curve
Inverse-T 1:Reset
Inverse-T 1:Time dial
Inverse-T 1:Additional
time delay
Inverse-T 1:Effect. by AR
off/n.ready
Inverse-T 1:Stage
blocked
Inverse-T 1:Effected by
AR cycle 1
Inverse-T 1:Stage
blocked
Inverse-T 1:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
5 A @ 100 Irated 0.05 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Inverse-T 1:Time dial
Inverse-T 1:Effected by
AR cycle 2
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
Setting Options
•
3I0 calculated
•
IN measured
•
off
•
on
•
test
•
no
•
yes
•
no
•
yes
•
no
•
yes
•
fundamental comp.
•
RMS value
0.010 A to 35.000 A
0.05 A to 175.00 A
0.001 A to 1.600 A
0.002 A to 8.000 A
0.00 s to 1.00 s
•
instantaneous
•
disk emulation
0.00 to 15.00
0.00 s to 60.00 s
•
no
•
yes
•
no
•
yes
•
no
•
yes
•
no
•
yes
0.010 A to 35.000 A
0.05 A to 175.00 A
0.001 A to 1.600 A
0.002 A to 8.000 A
0.00 to 15.00
•
no
•
yes
Default Setting
IN measured
off
no
no
no
fundamental
comp.
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
0.00 s
disk emulation
1.00
0.00 s
no
no
no
no
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.00
no