With the Activate device test mode parameter, you activate the test mode that adds a test bit to the
output indications. If test mode is activated but the test mode of the relay outputs is not, no relay outputs are
activated by the protection functions.
Parameter: Oper.bin.outp. under test
Default setting (_:151) Oper.bin.outp. under test = inactive
If you activate the parameter Oper.bin.outp. under test, you can permit the closing of a binary output
for test purposes. In this way, indications are output during a device-wide test mode and the relays are either
activated or not. If an individual function is in test mode, only indications are output and the relays are not
activated.
NOTE
i
i
The device remains in test mode during every startup until you intentionally set the device back into
process mode. You set process mode by switching the parameterActivate device test mode to inactive
again (removing the check mark).
3.10.2.3

Settings

Addr.
Device
_:101
_:102
_:138
Setting change
_:163
Spontan.indic.
_:139
Test support
_:150
_:151
3.10.2.4

Information List

No.
General
_:510
_:511
_:507
_:508
_:512
_:52
_:53
_:51
_:321
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
C
General:Rated frequency
General:Minimum
operate time
General:Block moni-
toring dir.
General:Reserv.time for
com.prot.
General:Fault-display
General:Activate device
test mode
General:Oper.bin.outp.
under test
Information
General:>Test mode on
General:>Test mode off
General:>Device funct.logoff on
General:>Dev. funct.logoff off
General:>LED reset
General:Behavior
General:Health
General:Test mode
General:Protection on
Setting Options
50 Hz
60 Hz
0.00 s to 60.00 s
off
on
0 s to 65535 s
with pickup
with trip
0
1
0
1
Data Class
(Type)
SPS
SPS
SPS
SPS
SPS
ENS
ENS
ENC
SPC
System Functions
3.10 Device Settings
Default Setting
50 Hz
0.00 s
off
120 s
with pickup
false
false
Type
I
I
I
I
I
O
O
C
C
167

Advertisement

Table of Contents
loading

This manual is also suitable for:

6md86