With the parameter Blk. w. inrush curr. detect., the stage can be stabilized against tripping on
transformer-inrush currents. If transformers are parts of the protection zones, set this parameter to yes.

Settings

7.25.9
Addr.
Inverse-T #
_:1
_:2
_:3
_:104
_:105
_:106
_:107

Information List

7.25.10
No.
Inverse-T #
_:81
_:52
_:53
_:54
_:56
_:300
_:59
_:55
_:57
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
C
Inverse-T #:Mode
Inverse-T #:Operate &
flt.rec. blocked
Inverse-T #:Threshold
Inverse-T #:Blk. w. inrush
curr. detect.
Inverse-T #:Type of char-
acter. curve
Inverse-T #:Reset
Inverse-T #:Time dial
Information
Inverse-T #:>Block stage
Inverse-T #:Behavior
Inverse-T #:Health
Inverse-T #:Inactive
Inverse-T #:Operate delay expired
Inverse-T #:Inrush blocks operate
Inverse-T #:Disk emulation running
Inverse-T #:Pickup
Inverse-T #:Operate
Protection and Automation Functions
7.25 Negative-Sequence Protection
Setting Options
off
on
test
no
yes
5.0 % to 999.9 %
no
yes
instantaneous
disk emulation
0.05 to 15.00
Data Class
(Type)
SPS
ENS
ENS
SPS
ACT
ACT
SPS
ACD
ACT
Default Setting
off
no
10.0 %
no
disk emulation
1.00
Type
I
O
O
O
O
O
O
O
O