Figure 6-17
The meaning of abbreviations can be found in
The indication Command active can also be routed to a binary output. This binary output is always active if
either an On or trip command is pending, or the switching device was selected by the command control.
6.2.2.4
Settings
Addr.
Ref. for %-values
_:2311:101
_:2311:102
Breaker settings
_:2311:112
_:2311:113
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Routing of the 1-Pole in DIGSI
Parameter
C
General:Rated
normal current
General:Rated
voltage
General:Current
1 A @ 100 Irated 0.030 A to 10.000 A
thresh. CB open
5 A @ 100 Irated 0.15 A to 50.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
General:1-pole
operate allowed
Table 6-8
and
Table
6-9.
Setting Options
0.20 A to 100000.00 A
0.20 kV to 1200.00 kV
0.030 A to 10.000 A
0.15 A to 50.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
•
no
•
yes
Control Functions
6.2 Switching Devices
Default Setting
1000.00 A
400.00 kV
0.100 A
0.50 A
0.100 A
0.50 A
0.100 A
0.500 A
yes