System Functions
3.6 Date and Time Synchronization
[sctimedg-220415, 1, en_US]
Figure 3-71
For every time source, you see the following:
Last received time (with date)
Receipt time of the last received time telegram
Configured type of timer
Indication of timer outage or failure
Whether the device time is currently synchronized from the time source
The lower section displays the device time, which is continuously updated. If the internal device time and the
infeed time source were synchronous at the time of telegram receipt, both displayed times are identical.
NOTE
i
i
All times displayed (also the time source) take into consideration the local time settings (zone and daylight
saving time of the device) in the form of a numerical offset for UTC (universal time).

Application and Setting Notes

3.6.4
Parameter: Date Format
Default setting Date format = YYYY-MM-DD
With the Date format parameter, you define the local customary format of the date display.
Parameter Value
YYYY-MM-DD
YYYY-MM-DD
YYYY-MM-DD
Parameter: Time zone time source 1,Time zone time source 2
Default setting Time zone time source 1 = local, Time zone time source 2 = local
With the Time zone time source 1 and Time zone time source 2 parameters, you define the
handling of time zones of the external timer.
132
Time Information in DIGSI
Description
Day.Month.Year: Typical European display
Example: 24.12.2010
Month/Day/Year: Typical US representation
Example: 12/24/2010
Year-Month-Day: Typical Chinese display
Example: 2010-12-24
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017