Information List - Siemens 6MD85 Manual

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Addr.
Synchr. conditions
_:5071:122
_:5071:123
_:5071:117
_:5071:118
_:5071:124
_:5071:125
6.4.7.4

Information List

No.
Synchrocheck 1
_:5071:81
_:5071:500
_:5071:502
_:5071:503
_:5071:504
_:5071:506
_:5071:505
_:5071:507
_:5071:508
_:5071:501
_:5071:54
_:5071:52
_:5071:53
_:5071:328
_:5071:324
_:5071:305
_:5071:325
_:5071:326
_:5071:327
_:5071:307
_:5071:306
_:5071:308
_:5071:309
_:5071:310
_:5071:311
_:5071:312
_:5071:313
_:5071:314
_:5071:315
_:5071:316
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
C
Synchrocheck 1:Max.
voltage diff. V2>V1
Synchrocheck 1:Max.
voltage diff. V2<V1
Synchrocheck 1:Max.
frequency diff. f2>f1
Synchrocheck 1:Max.
frequency diff. f2<f1
Synchrocheck 1:Max.
angle diff. α2>α1
Synchrocheck 1:Max.
angle diff. α2<α1
Information
Synchrocheck 1:>Block stage
Synchrocheck 1:>Selection
Synchrocheck 1:>Start / stop syn.proc.
Synchrocheck 1:>Start syn. process
Synchrocheck 1:>Stop syn. process
Synchrocheck 1:>Op. mode 'V1<V2>'
Synchrocheck 1:>Op. mode 'V1>V2<'
Synchrocheck 1:>Op. mode 'V1<V2<'
Synchrocheck 1:>Op. mode 'dir.cls.cmd'
Synchrocheck 1:>Block close command
Synchrocheck 1:Inactive
Synchrocheck 1:Behavior
Synchrocheck 1:Health
Synchrocheck 1:In progress
Synchrocheck 1:Release close cmd.
Synchrocheck 1:All sync. conditio. OK
Synchrocheck 1:Voltage difference OK
Synchrocheck 1:Angle difference OK
Synchrocheck 1:Frequency diff. OK
Synchrocheck 1:Cond. V1<V2> fulfilled
Synchrocheck 1:Cond. V1>V2< fulfilled
Synchrocheck 1:Cond. V1<V2< fulfilled
Synchrocheck 1:Frequency f1 > fmax
Synchrocheck 1:Frequency f1 < fmin
Synchrocheck 1:Frequency f2 > fmax
Synchrocheck 1:Frequency f2 < fmin
Synchrocheck 1:Voltage V1 > Vmax
Synchrocheck 1:Voltage V1 < Vmin
Synchrocheck 1:Voltage V2 > Vmax
Synchrocheck 1:Voltage V2 < Vmin
6.4 Synchronization Function
Setting Options
0.000 V to 170.000 V
0.000 V to 170.000 V
0.000 Hz to 2.000 Hz
0.000 Hz to 2.000 Hz
0 ° to 90 °
0 ° to 90 °
Data Class
(Type)
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
ENS
ENS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
Control Functions
Default Setting
5.000 V
5.000 V
0.100 Hz
0.100 Hz
10 °
10 °
Type
I
I
I
I
I
I
I
I
I
I
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
379

Advertisement

Table of Contents
loading

This manual is also suitable for:

6md86

Table of Contents