Settings; Information List - Siemens 6MD85 Manual

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Stage
2
7.13.5

Settings

Addr.
Definite-T 1
_:181:1
_:181:2
_:181:9
_:181:8
_:181:101
_:181:3
_:181:4
_:181:6
Definite-T 2
_:182:1
_:182:2
_:182:9
_:182:8
_:182:101
_:182:3
_:182:4
_:182:6
7.13.6

Information List

No.
Group indicat.
_:4501:55
_:4501:57
Definite-T 1
_:181:81
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
1.5 V
rated
Parameter
C
Definite-T 1:Mode
Definite-T 1:Operate &
flt.rec. blocked
Definite-T 1:Measured
value
Definite-T 1:Method of
measurement
Definite-T 1:Pickup mode
Definite-T 1:Threshold
Definite-T 1:Dropout
ratio
Definite-T 1:Operate
delay
Definite-T 2:Mode
Definite-T 2:Operate &
flt.rec. blocked
Definite-T 2:Measured
value
Definite-T 2:Method of
measurement
Definite-T 2:Pickup mode
Definite-T 2:Threshold
Definite-T 2:Dropout
ratio
Definite-T 2:Operate
delay
Information
Group indicat.:Pickup
Group indicat.:Operate
Definite-T 1:>Block stage
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
Setting Values
0.1 s to 0.2 s
Setting Options
off
on
test
no
yes
phase-to-ground
phase-to-phase
fundamental comp.
RMS value
1 out of 3
3 out of 3
0.300 V to 340.000 V
0.90 to 0.99
0.00 s to 300.00 s
off
on
test
no
yes
phase-to-ground
phase-to-phase
fundamental comp.
RMS value
1 out of 3
3 out of 3
0.300 V to 340.000 V
0.90 to 0.99
0.00 s to 300.00 s
Data Class
(Type)
ACD
ACT
SPS
Default Setting
off
no
phase-to-phase
fundamental
comp.
1 out of 3
110.000 V
0.95
3.00 s
off
no
phase-to-phase
fundamental
comp.
1 out of 3
130.000 V
0.95
0.50 s
Type
O
O
I
787