System Functions
3.4 Fault Recording
Parameter: Scaling COMTRADE
•
Recommended setting value Scaling COMTRADE = Secondary values
With the Scaling COMTRADE parameter, you scale the fault record data for the COMTRADE format. Possible
setting values are Primary values or Secondary values.
Settings
3.4.5
Addr.
General
_:2731:1
Control
_:2761:130
_:2761:131
_:2761:111
_:2761:112
_:2761:113
_:2761:116
_:2761:140
Information List
3.4.6
No.
Binary IO
_:2731:51
_:2731:52
_:2731:53
Binary IO
_:2761:300
_:2761:305
_:2761:306
_:2761:502
_:2761:503
_:2761:310
_:2761:311
_:2761:314
_:2761:327
96
Parameter
General:Mode
Control:Fault recording
Control:Storage
Control:Maximum record
time
Control:Pre-trigger time
Control:Post-trigger time
Control:Manual record time
Control:Sampling
frequency
Information
General:Mode (controllable)
General:Behavior
General:Health
Control:Start record
Control:Reset memory
Control:Clear memory
Control:>External start
Control:>Manual start
Control:Fault number
Control:Recording started
Control:Record made
Control:Tmax reduced
C
Setting Options
•
on
•
test
•
with pickup
•
with pickup & AR cyc.
•
user-defined
•
always
•
with trip
0.20 s to 20.00 s
0.05 s to 4.00 s
0.05 s to 0.50 s
0.20 s to 20.00 s
•
8 kHz
•
4 kHz
•
2 kHz
•
1 kHz
SIPROTEC 5, High-Voltage Bay Controller, Manual
Default Setting
on
with pickup
always
5.00 s
0.50 s
0.50 s
0.50 s
2 kHz
Data Class
Type
(Type)
ENC
C
ENS
O
ENS
O
SPC
C
SPC
C
SPC
C
SPS
I
SPS
I
INS
O
SPS
O
SPS
O
SPS
O
C53000-G5040-C015-9, Edition 11.2017