Siemens 6MD85 Manual page 287

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

[scauser3-190214-01, 1, en_US]
Figure 5-82
Selecting the SUP Protocol
Select the Slave Unit Protocol (SUP). This protocol is responsible for the communication between the SIPROTEC
5 device and the RTD Unit.
[scauser4-220114-01-DE, 1, en_US]
Figure 5-83
Communication Settings
Make the communications settings for the relevant serial channels. For this, use the default settings specified
by the RTD box. Normally, you must adapt only the parameterization of the SIPROTEC 5 device to the settings
of the RTD box. Make sure that the setting values in both devices are the same. The settings of the Non-
flickering light (on/off): is not relevant for the RS485 interface.
NOTE
i
i
The driver for the USART module for the SUP protocol is not preinstalled as standard for the initial use of
this interface (following the firmware update).
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Insertion Position for a USART Module
Selecting the SUP Protocol
Function-Group Types
5.7 Function-Group Type Analog Units
287