If, for the time set in the Dropout delay curr.crit. parameter, the maximum phase current falls below
the threshold value Dropout threshold current, the parameter set for the Cold-load pickup detection
function block is also deactivated. As a result, if the load current is very low, the action time Dropout delay
curr.crit. of the >Activate cold-load indication can be shortened.

Application and Setting Notes (Cold-Load Pickup Detection)

5.8.10
NOTE
i
i
The settings and indications described in this chapter are only available when using the optional Cold-load
pickup detection function block.
Parameter: Operating mode
Default setting (_:101) Operating mode = I open
With the Operating mode parameter, you set the criteria with which the Closure-detection function block
operates.
Parameter Value
I open
CB and I open
Parameter: Dropout threshold current
Default setting (_:102) Dropout threshold current = 1.00 A
With the Dropout threshold current parameter, you set the threshold at which the output signal
Cold-load pickup is deactivated when the current in at least one phase falls below this threshold.
Parameter: Dropout delay current criterion
Default setting (_:103) Dropout delay curr.crit. = 600 s
With the Dropout delay curr.crit. parameter, you set the time for which the actual value must be
below the Dropout threshold current threshold so that the output signal Cold-load pickup can be
deactivated prematurely.
Parameter: Dropout delay CB closed
Default setting (_:104) Dropout delay CB closed = 3600 s
With the Dropout delay CB closed parameter, you set the action time for the dynamic parameter set
switching in the event of cold-load pickup detection.
Parameter: Min. CB open time
Default setting (_:105) Min. CB-open time = 3600 s
With the Min. CB-open time parameter, you set the time after which the dynamic parameter set is acti-
vated in the event of cold-load pickup when the line is opened.
298
Description
When the Current-flow criterion function block detects a clearing open
condition, the decision is made for pickup. For this setting, make sure that
the Current thresh. CB open parameter is set lower than the
possible load current. If this is not the case, open is detected continuously
and each fault current that exceeds the Current thresh. CB open
parameter is interpreted as closure.
Closure is detected if one of the following conditions is met:
Analysis of the circuit-breaker auxiliary contact detects a clearing open
condition in at least one phase.
The current-flow criterion detects a clearing open condition.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017