NOTE
i
i
Note that in the Master-Follower method, you must configure one device as the Master device and the
additional devices as Follower devices.
[sc_par_trafo_id, 1, en_US]
Figure 6-151
Step 3
•
Double-click
•
Double-click the first IEC 61850 station.
•
Change the IEC 61850 station name for example in parallel operation.
•
Change IEC 61850 Edition 1 to Edition 2.
[sc_par_stat_iec_edi, 1, en_US]
Figure 6-152
•
Confirm the conversion to IEC 61850 Edition 2 with
•
Use >> to assign the devices to the IEC 61850 station.
[sc_par_assign_syscon, 1, en_US]
Figure 6-153
•
Export the IEC 61850 station as an ICD file to the IEC 61850 System Configurator.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Adapting the Parallel Transformer ID in DIGSI
Add new station .
Selecting the IEC 61850 Edition
Assigning the Devices
Yes .
Control Functions
6.9 Voltage Controller