Figure 5-90
Now, set the port over which the SUP protocol runs. In addition, set the IP address of the RTD box (refer to the
following figure). This address must be set with the same value in the RTD box.
[scautcp5-220114-01-DE, 1, en_US]
Figure 5-91
Finally, load the configuration in the device.
5.7.9.3

Temperature Simulation without Sensors

Connect a resistor on the sensor terminals of the RTD unit. Using this resistor, simulate a constant tempera-
ture. The resistance value should be around 50 Ω to 200 Ω.
If you want to simulate a changeable temperature, connect an adjustable resistor of maximum 470 Ω instead
of a fixed resistor.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Analog Unit Instance
Setting the Port and IP Address
Function-Group Types
5.7 Function-Group Type Analog Units
291