8.3.6.4
Application and Setting Notes
Parameter: Threshold
•
Recommended setting value (_:3) Threshold = 25 V
The Threshold parameter is used to set the voltage which the device uses to recognize the calculated fault
voltage (V
) as a failure of the voltage sums. Siemens recommends using the default setting.
F
Parameter: Delay failure indication
•
Recommended setting value (_:6) Delay failure indication = 5.00 s
Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
8.3.6.5
Settings
Addr.
Supv. sum V
_:1
_:3
_:6
8.3.6.6
Information List
No.
Supv. sum V
_:82
_:54
_:52
_:53
_:71
Voltage Phase-Rotation Supervision
8.3.7
8.3.7.1
Overview of Functions
The Voltage phase-rotation supervision function monitors the phase sequence of the secondary-circuit
voltages by monitoring the sequence of the zero crossings (with same sign) of the voltages. This enables the
device to detect connections that were inverted during commissioning. The criterion for the check is the
setting of the Phase sequence parameter.
8.3.7.2
Structure of the Function
The Voltage phase-rotation supervision function is located in the Power-system data of each 3-phase
voltage measuring point.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
C
Supv. sum V:Mode
Supv. sum V:Threshold
Supv. sum V:Delay
failure indication
Information
Supv. sum V:>Block function
Supv. sum V:Inactive
Supv. sum V:Behavior
Supv. sum V:Health
Supv. sum V:Failure
8.3 Supervision of the Secondary System
Setting Options
•
off
•
on
•
test
0.300 V to 170.000 V
0.00 sto 100.00 s
Data Class
(Type)
SPS
SPS
ENS
ENS
SPS
Supervision Functions
Default Setting
off
43.300 V
5.00 s
Type
I
O
O
O
O
957