Stage Synchrocheck
6.4.7
6.4.7.1
Description
Checking Closing Conditions
[losynche-160311-01.tif, 1, en_US]
Figure 6-71
With this operating mode, the values ΔV, Δf, and Δα are checked before connecting the 2 parts of the elec-
trical power system. The indication All sync. conditio. OK signals that the setting values (conditions)
have been reached and that the release for closure has been given (see Checking the Closing Conditions,
Closure in chapter
Every fulfilled condition is signaled individually via the indications Voltage difference OK, Frequency
diff. OK, and Angle difference OK.
If a condition is not fulfilled, detailed information on why the condition is not fulfilled is provided via indica-
tions. If the differential voltage is outside the setting limits, for example, the indication V dif.too
large(V2<V1) is issued. The indication indirectly contains information that the voltage V2 has to be
increased for a successful synchronization.
With the Expanded delta-f options stage type configured and an activated (_:140) Limit dfdiff/dt
for sync. op parameter, the frequency difference rate of change is also checked. If the permissible
frequency change rate (parameter (_:141) Max. value dfdiff/dt syn) is exceeded, the indication
(_:329) dfdiff/dt too large is issued.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Closing Conditions for the Synchrocheck Function
6.4.6 Sequence of
Functions).
Control Functions
6.4 Synchronization Function
377