Control Functions
6.4 Synchronization Function
[lohyster-010415-01.vsd, 1, en_US]
If the Synchronization function is started within the hysteresis, no switching is performed as a result of the
minimum and maximum operating limit (parameters Min. operating limit Vmin and Max. operat.
limit Vmax). If the Synchronization function is started within the voltage operating range and the voltage
exceeds the minimum or maximum operating limit during the synchronization process, selecting can occur in
the area of the hysteresis.
Parameter: Max.durat. sync.process
Default setting (_:5071:110) Max.durat. sync.process = 30 s
The parameterized conditions must be fulfilled within this time. If the conditions are not fulfilled, no further
closing release takes place and the synchronization stage is stopped. If this time is set to ∞, the conditions are
checked until they are fulfilled. This is also the default setting. Observe the operating conditions when
defining the time limitation. This must be defined specifically for each system. If 0 or 0.01 s is set, then all
conditions are checked once at the starting time point. Thereafter the process is stopped immediately.
Parameter: Voltage adjustment
Default setting (_:5071:126) Voltage adjustment = 1.00
The parameter can be used for correction of amplitude errors, for example, due to indirect measurement (for
example, tap changer).
To apply a transformer between measuring points, the Voltage adjustment parameter is not needed. The
transformer ratios are set for the measuring points and the function will take them into account automatically.
Parameter: Angle adjust. (transform.)
Default setting (_:2311:127) Angle adjust. (transform.) = 0
The parameter can be applied under the following conditions:
1. Phase-angle rotation by power transformer between the measuring points
2. Correction of phase-angle errors
1. Phase-angle rotation by power transformer between the measuring points:
370
o
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017