Siemens 6MD85 Manual page 1044

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Measured Values, Energy Values, and Supervision of the Primary System
9.9 Energy Values
Parameter Value
True
Note: When the parameter is activated, the following setting values are possible for the parameter (_:111)
Energy restore interval: 1 min; 2 min; 3 min; 4 min; 5 min; 6 min; 10 min; 12 min; 15 min; 20 min;
30 min; 60 min.
Input Signals: >Restoring and >Resetting
Binary Inputs
>Restoring
>Reset
You route these logical signals in the DIGSI routing matrix. Open the function group, for example, Line, where
you created the energy value. There, under the tab Measured values you will find the tab Energy, 3-phase.
In this tab, you will find the logical signals in addition to the measured values.
1044
Description
The cyclic restoring after the set time of the parameter (_:111) Energy
restore intervalwill also be synchronized with the system time.
Example: Energy restore interval = 30 min; current system time:
12:10 o'clock First restore: 12:30 o'clock; next restore: 13:00 o'clock etc.
Description
The restoring of the metered values is initiated via a binary input.
The metered value memory is set to 0 through the binary input.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Advertisement

Table of Contents
loading

This manual is also suitable for:

6md86

Table of Contents