Parameter: Tilt power characteristic
Recommended setting value (_:6331:103) Tilt power characteristic = +20°
The Tilt power characteristic parameter is used to incline the pickup characteristic. In the example
(see
Figure
7-175), the power characteristic has a tilt of 20°. Set the Tilt power characteristic param-
eter to +20° (for a definition of the sign, see
Parameter: Dropout delay
Recommended setting value (_:6331:7) Dropout delay = 20 ms
The Dropout delay parameter maintains the pickup even if the measured value drops momentarily below
the threshold value. A delay is required for very low pickup values to prevent a so-called chattering of the
function. In the example, the setting value is 20 ms.
Parameter: Operate delay
Recommended setting value (_:6331:6) Operate delay = 100 ms
The Operate delay must be set for the specific application. In the example, a setting value of 100 ms has
been selected.

Settings

7.22.8
Addr.
Power P> 1
_:6241:1
_:6241:2
_:6241:104
_:6241:3
_:6241:101
_:6241:103
_:6241:7
_:6241:6
Power P< 1
_:6271:1
_:6271:2
_:6271:105
_:6271:3
_:6271:101
_:6271:103
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
Power P> 1:Mode
Power P> 1:Operate &
flt.rec. blocked
Power P> 1:Measured value
Power P> 1:Threshold
Power P> 1:Dropout ratio
Power P> 1:Tilt power char-
acteristic
Power P> 1:Dropout delay
Power P> 1:Operate delay
Power P< 1:Mode
Power P< 1:Operate &
flt.rec. blocked
Power P< 1:Measured value
Power P< 1:Threshold
Power P< 1:Dropout ratio
Power P< 1:Tilt power char-
acteristic
Figure
7-174).
C
Setting Options
off
on
test
no
yes
power of phase A
power of phase B
power of phase C
positive seq. power
-200.0 % to 200.0 %
0.90 to 0.99
-89.0 ° to 89.0 °
0.00 s to 60.00 s
0.00 s to 60.00 s
off
on
test
no
yes
power of phase A
power of phase B
power of phase C
positive seq. power
-200.0 % to 200.0 %
1.01 to 1.10
-89.0 ° to 89.0 °
Protection and Automation Functions
7.22 Power Protection (P,Q), 3-Phase
Default Setting
off
no
positive seq.
power
80.0 %
0.95
0.0 °
0.00 s
1.00 s
off
no
positive seq.
power
5.0 %
1.05
0.0 °
859