With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see chapter
Inversion of Output-Related Measured and Statistical Values):
Active energy, output: Wp+
Active energy, input: Wp-
Reactive energy, output: Wq+
Reactive energy, input: Wq-
9.9.2

Application and Setting Notes for Energy Values

The set parameters apply for all electricity meters of the device. You find the setting parameters in DIGSI in the
project tree under Settings > Device settings.
Parameter: Energy restore interval
Default setting: (_:111) Energy restore interval = 10 min
Parameter Value
0 min
60 min
Note: If the parameter is activated through a time setting, the parameter Energy restore time is not in
effect and will be deactivated automatically.
Parameter: Energy restore time
Default setting: (_:112) Energy restore time = none
Parameter Value
none
hh:00
hh:15
hh:30
hh:45
Note: If the parameter is activated through a time setting, the parameter Energy restore interval is
not in effect and will be deactivated automatically.
Parameter: Energy restore
Default setting: (_:120) Energy restore = latest value
Parameter Value
latest value
delta value
Parameter: Energy restore by A.time
Default setting: (_:121) Energy restore by A.time = false
Parameter Value
False
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Measured Values, Energy Values, and Supervision of the Primary System
Description
Restoring deactivated
Cyclical restoring after the set time 1 minute to 60 minutes
Description
Deactivated
Restoring on the full hour
Restoring 15 minutes after the full hour
Restoring 30 minutes after the full hour
Restoring 45 minutes after the full hour
Description
Restoring of the current energy value
Restoring the difference value between the current energy value and the
energy value of the last restoring operation
Description
Restoring deactivated
9.2 Structure of the
Function, section on the
9.9 Energy Values