Voltage Measuring-Point Selection; Overview Of Functions; Function Description - Siemens 6MD85 Manual

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Function-Group Types

5.9 Voltage Measuring-Point Selection

5.9
Voltage Measuring-Point Selection

Overview of Functions

5.9.1
The function block Voltage measuring-point selection can:
Provide the ability to switchover the voltage measuring points to be applied, if various voltage measuring
points are connected to the voltage interface of the function group
Select the correct voltage based on the switch position of the plant
If more than one voltage measuring points are connected to the same voltage interface of the function group,
use the Voltage measuring-point selection function block in the function group to select the correct voltage
based on the switch position of the plant.
The Voltage measuring-point selection is a common functionality for the function groups of the protected
objects.

Function Description

5.9.2
The Voltage measuring-point selection function block realizes the selection of voltage measuring points by a
logic block chart. The logic block chart controls the input
tions of disconnectors.
Example
Figure 5-99
shows an example of voltage measuring points selection for the function group Capacitor bank in
a double busbar application.
[dwbusbardouble.vsd, 2, en_US]
Figure 5-99
Connecting Measuring Points to Capacitor Bank Function Group
Figure 5-100
shows the connection of the function group Capacitor bank with several measuring points in
DIGSI. The ID of each measuring point appears in the bracket after the name.
300
Double Busbar with Capacitor Bank
>MP-ID selection depending on the switch posi-
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017