V/I-Measuring-Transducer Unit with Fast Inputs

5.7.6.1

Overview

The fast analog measuring-transducer inputs process voltage values (DC -10 V to +10 V) as well as current
values (DC -20 mA to 20 mA).
The function MT fast input:
Provides sampled values for recording in the fault record (the maximum sampling frequency is 8 kHz for
all other SIPROTEC 5 devices). The recorded sampling frequency results from the setting of the fault-
recorder function.
Calculated measured values from the sampled values. These measured values have been deduced from
the arithmetic mean values. The measuring range for the mean-value calculation is adjustable in the
interval from 10 ms to 100 ms.