Settings; Information List; Circuit Breaker; Overview - Siemens 6MD85 Manual

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
5.6.4.3

Settings

Addr.
Trip logic
_:101
_:102
_:103
5.6.4.4

Information List

No.
Trip logic
_:300

Circuit Breaker

5.6.5
5.6.5.1

Overview

The Circuit-breaker function block represents the physical switch in the SIPROTEC 5 device.
The basic tasks of this function block are the operation of the circuit breaker and the acquisition of the circuit-
breaker auxiliary contacts and other circuit-breaker information.
The Circuit-breaker function block also provides information about:
Number of switching cycles
Breaking current, breaking voltage, and breaking frequency
Summation breaking current
5.6.5.2

Tripping, Opening, and Closing the Circuit Breaker

The circuit breaker is operated in the following situations:
Tripping of the circuit breaker as a result of a protection trip command
Opening of the circuit breaker as a result of control operations
Closing of the circuit breaker as a result of automatic reclosing or control operations
Tripping is always the result of a protection function. The operate indications of the individual protection func-
tions are summarized in the Trip logic function block. The trip command that causes the tripping in the
Circuit breaker function block is generated there. 1-pole or 3-pole tripping is possible depending on the
configuration, parameterization or even the protection function (see also
To operate the circuit breaker, the Circuit-breaker function block provides the output signals (see
that must be routed to the corresponding binary outputs of the device.
236
Parameter
Trip logic:Trip at 2ph short
circuit
Trip logic:3-pole coupling
Trip logic:Reset of trip
command
Information
Trip logic:Trip indication
C
Setting Options
3-pole
1-pole, leading phase
1-pole, lagging phase
with pickup
with trip
with I<
with I< & aux.contact
with dropout
5.6.4.1 Function Description
SIPROTEC 5, High-Voltage Bay Controller, Manual
Default Setting
3-pole
with trip
with I<
Data Class
Type
(Type)
ACT
O
Table
C53000-G5040-C015-9, Edition 11.2017
).
5-7)