WAGO I/O-SYSTEM 750 Manual page 93

Fieldbus independent i/o modules bluetooth rf transceiver
Table of Contents

Advertisement

* The addresses stated in the table correspond to the process data allocation given in the
configuration.
If the PROFIBUS master is a Siemens S7 SPS, the data is consistently read
and written with the system functions SFC14 and SFC15.
To map the input data EW20 through EW30 to the flag area MW100 through
MW110, the functions are accessed as follows:
CALL SFC 14
LADDR := W#16#14 (read from input address EW20)
RECORD := P#M100.0 BYTE 12 (write 12 bytes beginning with MW100)
RET_VAL := MW112 (write error messages after MW112)
To map the output data AW10 through AW20 to the flag area MW114
through MW124, the functions are accessed as follows:
WAGO-I/O-SYSTEM 750
I/O Modules
no.
Function
4
Analog input
Analog input
5
Potential input
6
Control/status byte
Mailbox
Mailbox
Mailbox
Data
Data
7
Potential input
8
Analog output
Analog output
9
Analog input
Analog input
10
Analog output
Analog output
11
Analog input
Analog input
12
Potential input
13
Digital output
Digital output
Digital output
Digital output
14
End Module
Fieldbus-specific Additions
Module
Identifier
750-452 2 AI/0...20 mA/diff.
0x51
Potential input
®
750-644 Bluetooth
RF Trans-
ceiver
12 byte process image
0x8B
Potential input
750-550 2 AO/0...10 V
0x61
750-452 2 AI/0...20 mA/diff.
0x51
750-550 2 AO/0...10 V
0x61
750-452 2 AI/0...20 mA/diff.
0x51
Potential input
750-504 4 DO/24 V DC/0.5 A
0x20
End Module
PROFIBUS-DP
Process image of the master *
inputs
outputs
EW 0
-
EW 2
-
-
-
EW 20
AW 10
EW 22
AW 12
EW 24
AW 14
EW 26
AW 16
EW 28
AW 18
EW 30
AW 20
-
-
-
AW 0
-
AW 2
EW 4
-
EW 6
-
-
AW 4
-
AW 6
EW 8
-
EW 10
-
-
-
-
AB8.0
-
AB8.1
-
AB8.2
-
AB8.3
-
-
• 93