WAGO I/O-SYSTEM 750 Manual page 173

Fieldbus independent i/o modules bluetooth rf transceiver
Table of Contents

Advertisement

Return values
Parameter
MBX_NETWORK
_STATE
W0 ...W6
W7
E0...E5
E6, E7
Note
W0 to W6 correspond to WAGO devices 0x20 to 0x26 with
MBX_TARGET_TABLE_AND_INDEX.
E0 to E5 correspond to external devices 0x10 to 0x16 with
MBX_TARGET_TABLE_AND_INDEX.
WAGO-I/O-SYSTEM 750
I/O Modules
Value
MBX_NETWORK_FAILED
(0x01)
MBX_NETWORK_OK
(0x02)
MBX_NETWORK_
INCONSISTENT (0x03)
Assigned bit = 1
Assigned bit = 0
0
Assigned bit = 1
Assigned bit = 0
0
Mailbox Command References
Description
Configured network not established
(e.g., in configuration mode)
Configured network successfully estab-
lished.
At least one, but not all, configured
connections could be established.
Assigned device from the table of
WAGO devices is linked and con-
nected.
Assigned device from the table of
WAGO devices is not connected.
Reserved
Assigned device from the table of ex-
ternal devices is linked and connected.
Assigned device from the table of ex-
ternal devices is not connected.
Reserved
Appendix
• 173

Advertisement

Table of Contents
loading

Table of Contents