WAGO I/O-SYSTEM 750 Manual page 76

Fieldbus independent i/o modules bluetooth rf transceiver
Table of Contents

Advertisement

76 •
Tools for Configuring and Operating
Configuring and Operating with WAGO-I/O-CHECK
Status
Signal Strength
Available Channels
Click on one of the fields of the last column of the table. A dialog with a de-
tailed status display for the selected slot opens (see Figure 34). Choose For all
connections by checking it to query the status of all slots.
Figure 34: Status query for slots
By selecting a certain Object group, you are limiting the status reports ac-
cordingly (see Table 34).
Table 34: Object groups and possible status reports
Object Groups
Whole system
Wireless connections
Value
Description
-127...0
RSSI value/signal strength too weak
0
Signal strength very good
0...+127
Signal strength too strong
(see Appendix 6.3.6.5, "GetLinkSignalStrength")
< 39
Too many busy/defective channels
39...53
Some busy/defective channels
> 53
Free/undisturbed channels (low interference)
(see Appendix 6.3.6.6, "GetAvailableChannelMap")
Status *
Ok
Ok
Not specified
BER is moderate
BER is high
Less than 39 channels available
Less than 54 channels available
Connection error
Connection interrupted