6. 33 Adjustment parameters

6. 33. 1
Pulse output based on input cumulative power by a
fixed integral value
<F667: Pulse output step of input cumulative power>
<F668: Pulse output width of input cumulative power>
■ Function
Every time the integral input power reaches the cumulative power unit set by <F667: Pulse output
step of input cumulative power>, pulse signal can be output. You can display the power by pulse
count without an external power meter.
Pulse output width is set by <F668: Pulse output width of input cumulative power>.
■ Parameter setting
Title
Parameter name
F667
Pulse output step of input
cumulative power
F668
Pulse output width of
input cumulative power

■ Setting the parameters

This is a setting for pulse output from terminal [FP].
 Set <F130: Terminal FP function 1> = "180: For input cumulative power"
Set the integral power unit with <F667: Pulse output step of input cumulative power>, and set the
pulse output width with <F668: Pulse output step of input cumulative power>.
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Reference
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].
F667 : Pulse step of input power
0: 0.1kwh
1: 1kWh
2: 10kWh
3: 100kWh
4: 1000kWh
Adjustment range
0: 1.0=1 kWh
1: 1.0=10 kWh
2: 1.0=100 kWh
3: 1.0=1000 kWh
4: 1.0=10000 kWh
5: 1.0=100000 kWh
0.1 - 1.0
6-159
E6582062
STOP
0.0Hz
14:10
Unit
Default setting
1
s
0.1
6. [Advanced] How to use parameters
3
4
6
9