Toshiba TOSVERT VF-AS3 Instruction Manual page 245

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 1. 2
Output a signal when reached to a frequency
command (output the Acc/Dec completed signal)
<F102: Reach signal detection band>
■ Function
When the output frequency becomes the frequency command ±<F102: Reach signal detection
band>, the Acc/Dec completed signal is output from the output terminal.
■ Parameter setting
Title
Parameter name
F102
Reach signal detection
band
Frequency command value +
Frequency command value
Frequency command value -
Terminal [FP]
(Acc/Dec completed)
Terminal [F]
(Fwd run)
■ Output terminal parameter setting
Acc/Dec completed signal is the default setting for output terminal [FP].
Title
Parameter name
F130
Terminal FP function 1
*1
For details on the output terminal functions, refer to [7. 2. 2].
Adjustment range
0.0-FH
Output frequency (Hz)
<F102>
<F102>
0
*1
0-255
6-3
STOP
F102 : Reach signal detect band
Min: 0.0
X1000
X100
Unit
Hz
Time (s)
ON
OFF
ON
OFF
Adjustment range
6. [Advanced] How to use parameters
E6582062
0.0Hz
12:43
2.5
Hz
Max: 80.0
X10
X1
3
4
6
Default setting
2.5
9
Default setting
6