Toshiba TOSVERT VF-AS3 Instruction Manual page 415

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 34. 8
Clearing run command
<F719: Run command clear select>
■ Function
This parameter is used to select whether the run command is retained or cleared when the following
events occur during panel run or RS485 communication run.
• Coast stop with standby function (ST) is off (OFF display)
• Coast stop with coast command function (FRR) is on (OFF display)
• Power circuit undervoltage (MOFF) alarm
■ Parameter setting
Title
Parameter name
F719
Run command clear
select
■ Difference between the settings
<F719> setting value
0
1
2
3
• If "PrA" alarm occurs when STO activated, run command is cleared regardless of the <F719>
setting.
Important
0: Clear at coast stop. Retain when MOFF
occurs and CMOd is changed.
1: Retain run command.
2: Clear at coast stop and at MOFF. Retain
when CMOd is changed.
3: Clear at coast stop, at MOFF and when
CMOd is changed.
Coast stop
undervoltage (MOFF)
Run command clear
Retain run command
Run command clear
6-173
STOP
F719 : Run command clear select
0: Clr at coast stop
1: Retain run command
2: Clr at coast stop & MOFF
3: Clr at coast stop, MOFF & Cmod
Adjustment range
When power circuit
alarm occurred
Retain run command
Retain run command
Run command clear
6. [Advanced] How to use parameters
E6582062
0.0Hz
14:14
Default setting
2
When <CMOd> is
changed
3
4
6
9