<F613: Short circuit detection at start>
<F614: Pulse width of short circuit detection at start>
■ Function
Inverter detects inverter output short-circuit at the start.
4
Normally, short-circuit can be detected in the length of standard pulse (50 μs). When operating a
low-impedance motor, such as a high-speed motor, however, select the short-time pulse by
<F614:Pulse width of short circuit detection at start> to prevent an error detection.
4
■ Parameter setting
6
Title
F613
9
F614
■ Setting the <F613: Short circuit detection at start>
0: At every startup by standard pulse
Detection is executed in the length of standard pulse every time at the start of inverter operation.
1: Only one time after power on by standard pulse
Detection is executed in the length of standard pulse only during the first start-up at power on or
after resetting.
2: At every startup by F614 setting pulse
Detection is executed in the length of short-time pulse specified by <F614: Pulse width of short
circuit detection at start> every time at the start of inverter operation.
3: Only one time after power on by F614 setting pulse
Detection is executed in the length of short-time pulse specified by <F614: Pulse width of short
circuit detection at start> only one time during the first start-up at power on or after resetting.
6. [Advanced] How to use parameters
Short circuit detection at start
Parameter name
Short circuit detection at
start
Pulse width of short
circuit detection at start
F613 : Startup short circuit detect
0: At every startup by std pulse
1: 1 time at power on by std pulse
2: At every startup by F614 pulse
3: 1 time at power on by F614
Adjustment range
0: At every startup by standard pulse
1: Only one time after power on by standard
pulse
2: At every startup by F614 setting pulse
3: Only one time after power on by F614
setting pulse
0: No short circuit detection at start
in case F613="2", or "3"
1 - 50
6-132
E6582062
STOP
0.0Hz
13:56
Unit
Default setting
0
25
μs