Retain run command.
Inverter restarts when coast stop is cleared after its occurrence.
Inverter restarts when power is supplied again when the power circuit undervoltage (MOFF) alarm
occurs.
Run command clear
Inverter does not restart after coast stop or occurrence of the power circuit undervoltage (MOFF)
alarm.
Press the [RUN] key to operate it again in panel run. Turn on the run command in RS485
communication run.
■ Setting example of parameters of input terminals
Set necessary function to the unused input terminal. For details, refer to [7. 2. 1].
"6: Standby"
"96: Coast stop"
4
4
Reference
6
9
6. [Advanced] How to use parameters
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• <CMod: Run command select> -> Refer to [5. 2. 1]
• Details of operation by external signals -> Refer to Chapter 7
6-174