Toshiba TOSVERT VF-AS3 Instruction Manual page 86

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

■ With frame size A8
VFAS3-4200KPC to 4280KPC
1
Remove the front cover and the transparent cover inside
(transparent resin).
For how to remove, refer to [2. 2. 5].
2
Remove the screw for switching of grounding capacitor
from the position of the grounding mark and tighten it to
the position of the grounding mark.
The grounding capacitor's capacity is increased.
2
3
To recover the shipping state, remove the screw(s) for
switching of grounding capacitor and tighten it/them to the
screw hole in the position of the non-grounding mark.
The grounding capacitor's capacity is reduced.
4
After switching, mount the transparent cover and the front
cover in this order.
For how to mount, refer to [2. 2. 5].
9
Prohibited
Note) If a neutral grounding system is used, changing the connection of the grounding
capacitor as shown in the figure at the top (changing the capacitance from Small to Large)
makes the inverter compliant with the EMC directive.
2. Installation and wiring
• In case of one phase grounding system (A three-phase supply power is connected in delta), do
not change the connection of grounding capacitor before factory setting. If connection changed
(this means the capacitance is increased), the capacitor may become damaged.
Capacity small
Capacity large
CAUTION
2-52
E6582062