Setting Functions Of Operation Panel - Toshiba TOSVERT VF-AS3 Instruction Manual

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 34 Setting functions of operation panel

Lock or unlock the key operation of the operation panel and parameter setting.
Also, set the display functions of the operation panel.
6. 34. 1
<F700: Parameter reading&writing access lockout>
<F730: Panel frequency setting lockout>
<F731: Operation after disconnection detection during
panel run>
<F732: Panel Hand/Auto function lockout>
<F733: Panel Run lockout>
4
<F734: Panel emergency off lockout>
<F735: Panel reset lockout>
<F736: CMOd/FMOd change lockout during run>
4
<F737: Panel keys lockout>
<F738: Password setting>
6
<F739: Password verification>
■ Function
These parameters allow you to locked or unlocked operation on the operation panel and the change
of parameters. Using these parameters, you can also lock various key operations to prevent
malfunction.
Lock parameters with a password to prevent configuration.
9
■ Parameter setting
Title
F700
F730
F731
F732
F733
F734
6. [Advanced] How to use parameters
Lockout key operation and parameter setting
Parameter name
Parameter
reading&writing access
*1
lockout
Panel frequency setting
lockout
Operation after
disconnection detection
*2
during panel run
Panel Hand/Auto
*3
function lockout
Panel Run lockout
Panel emergency off
lockout
F700 : Parameter read&write lock
0: Unlocked
1: Writing locked (Op & Ext panel)
2: Writing locked (1+RS485)
3: Read&Write locked (panel)
4: Read&Write locked (3+RS485)
Adjustment range
0: Unlocked
1: Writing locked (Operation panel, Extension
panel)
2: Writing locked (1+RS485)
3: Reading&Writing locked (Operation panel,
Extension panel)
4: Reading&Writing locked (3+RS485)
0: Unlocked
1: Locked
2: Unlocked after press OK
1: Continue running
2, 3: -
4: Trip
0: Unlocked
1: Locked
0: Unlocked
1: Locked
0: Unlocked
1: Locked
6-164
E6582062
STOP
0.0Hz
14:12
Default setting
0
2
4
1
0
0