Toshiba TOSVERT VF-AS3 Instruction Manual page 80

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

■ With frame size A1
VFAS3-2004P to 2022P, VFAS3-4004PC to 4037PC
1
Remove the front cover.
For how to remove, refer to [2. 2. 1].
2
Remove two screws for switching of grounding
capacitor.
The grounding capacitor is disconnected.
Mount the removed screws to the positions shown
in the figure on the right and tighten them.
2
3
To recover the shipping state, mount the two
screws for switching of grounding capacitor and
tighten them.
The
grounded.
4
After switching, mount the front cover.
For how to mount, refer to [2. 2. 1].
Important
9
2. Installation and wiring
grounding
capacitor
is
• For models with two switching screws, be sure to set both screws to the same side.
Grounding
Screw
Non-grounding
connected
and
2-46
E6582062
Screw