Setting the upper and lower limits of the output frequency
<UL: Upper limit frequency>
<LL: Lower limit frequency>
4
5
■ Function
Set the upper limit frequency to decide the upper limit of the output frequency and the lower limit fre-
quency to decide the lower limit.
■ Parameter setting
9
Title
UL
LL
*1
Depending on the setup menu. Refer to [5. 3. 10].
■ Guideline for the setting
Set <UL: Upper limit frequency> to a value which is ten times or less the values of <vL: Base
frequency 1>.
If the output frequency is exceeding to 10 times of <vL>, the "A-05" alarm will appear, and the value
of the output frequency will be limited to a value which is 10 times the value of <vL: Base frequency
1>.
The same holds for Base frequency 2 - 4. (Refer to [6. 4].)
5. [Fundamental operation] How to use parameters
Basic parameter
Basic parameter
Parameter name
Upper limit frequency
Lower limit frequency
Easy mode
Easy mode
Adjustment range
0.0 - FH
0.0 - UL
5-10
E6582062
STOP
0.0Hz
UL
:Upper limit frequency
60.0
Min: 0.0
Max: 80.0
X1000
X100
X10
STOP
0.0Hz
LL
:Lower limit frequency
0.0
Min: 0.0
Max: 60.0
X1000
X100
X10
Unit
Hz
50.0/60.0
Hz