• Coast stop is a stop pattern where the inverter output is turned OFF, and the motor rotation
stops spontaneously.
The deceleration stop is performed by default setting (the frequency is decreased to 0 Hz by
the inverter deceleration time).
• When "ST" (standby) is turned OFF, the motor performs coast stop.
• "ST"(standby)is always ON by default setting. Therefore, change the setting as shown below:
 - <F110: Always active function 1> = "0: No function"
 - Assign "6: ST" (standby) to an unused input terminal.
• When the terminal where "ST" (standby) is assigned is turned OFF, coast stop will be
performed.
Memo
Terminal [F]
(Fwd run)
Input terminal
(Standby)
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Reference
• Procedure to change parameter setting -> Refer to [4. 2. 3].
• Details on operation by external signals -> Refer to [Chapter 7].
Motor speed
6-13
Coast stop
Time (s)
ON
OFF
ON
OFF
6. [Advanced] How to use parameters
E6582062
3
4
6
9