Selecting how to input a frequency command
<FMOd: Frequency command select 1>
Basic parameter
■ Function
Select where to input a frequency command to the inverter.
■ Parameter setting
Title
Parameter name
FMOd
Frequency command
select 1
■ Selecting a setting value
1: Terminal RR
Analog signal: Input a frequency command with 0 - 10 Vdc.
For details of the control terminal, refer to [2. 3. 5].
For details of operation by external signals, refer to "Chapter 7".
2: Terminal RX
Analog signal: Input a frequency command with -10 to +10Vdc.
For details of the control terminal, refer to [2. 3. 5].
For details of operation by external signals, refer to "Chapter 7".
3: Terminal II
Analog signal: Input a frequency command with 4 - 20 mAdc (0 - 20 mAdc).
For details of the control terminal, refer to [2. 3. 5].
Easy mode
Adjustment range
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 9: -
10: Touch wheel 1 (power off or press OK to
save)
11: Touch wheel 2 (press OK to save)
12: Sr0
13, 14: -
15: Terminal Up/Down frequency
16: Pulse train
17: High resolution pulse train (option)
18, 19: -
20: Embedded Ethernet
21: RS485 communication (connector 1)
22: RS485 communication (connector 2)
23: Communication option
5-3
5. [Fundamental operation] How to use parameters
E6582062
STOP
0.0Hz
FMOd :Frequency command select 1
1: Terminal RR
2: Terminal RX
3: Terminal Ⅱ
4: Terminal AI4(option)
5: Terminal AI5(option)
1
15:06
3
4
Default
5
setting
9