Toshiba TOSVERT VF-AS3 Instruction Manual page 234

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

2: Terminal ST On/Off
The motor speed and direction of rotation of the coasting motor are detected to start it smoothly
(motor speed search function).
The input terminal to which "ST: Standby" is assigned is turned off. It is operated when the input
4
terminal is turned on again. Turn on the run command.
Since "ST: Standby" is always ON in default setting, make setting as follows.
• Set <F110: Always active function 1> to "0: No function" (Refer to [6. 3. 1])
5
• Assign "6: ST: Standby" to an unused input terminal
For assignment of a function to an input terminal, refer to [7. 2. 1].
9
3: Terminal ST On/Off or power failure
It is operated both in "1" and "2"
4: At startup
A motor speed search is executed each time at startup.
When the motor is rotated by the external factor before running by the inverter, it can be started without
trip.
5. [Fundamental operation] How to use parameters
Output frequency
Motor speed
Terminal [F] or [R]
(Run command)
Motor speed
Terminal [F] or [R]
(Run command)
Input terminal
(Standby)
5-68
E6582062
ON
OFF
ON
OFF
ON
OFF