6. 4
<F170: Base frequency 2>
<F171: Base frequency voltage 2>
<F172: Manual torque boost 2>
<F174: Base frequency 3>
<F175: Base frequency voltage 3>
<F176: Manual torque boost 3>
<F178: Base frequency 4>
<F179: Base frequency voltage 4>
<F180: Manual torque boost 4>
<F182: Motor overload protection current 2>
4
<F183: Motor overload protection current 3>
<F184: Motor overload protection current 4>
4
6
■ Function
These parameters are used for setting when you want to switch up to four types of motors for an
inverter, or when you want to switch the motor V/f characteristics (four types) according to the
9
purpose or operation method.
V/f1 to V/f4 are switched by the input terminal signals.
Memo
■ Parameter setting
Title
F170
F171
F172
F174
F175
6. [Advanced] How to use parameters
Switching two to four types of motor
characteristics
• <Pt: V/f Pattern> is valid only for V/f1.
When V/f2 to V/f4 are selected, V/f constant control is applied regardless of the setting of <Pt>.
• Do not switch the motors when <Pt: V/f Pattern> is set to "7" or "8".
• For the parameters that are selected when V/f1 to V/f4 are switched, refer to the following table.
Parameter name
Base frequency 2
Base frequency voltage 2
Manual torque boost 2
Base frequency 3
Base frequency voltage 3
F170 : Base frequency 2
Min: 15.0
X1000
F171 : Base frequency voltage 2
Min: 50
X1000
Adjustment range
15.0-590.0
240V class: 50-330V
480V class: 50-660V
0.00-30.00
15.0 - 590.0
240V class: 50-330V
480V class: 50-660V
6-16
E6582062
STOP
0.0Hz
12:49
60.0
Hz
Max: 590.0
X100
X10
X1
STOP
0.0Hz
12:53
400
V
Max: 660
X100
X10
X1
Unit
Default setting
Hz
*1
50.0/60.0
V
*1
%
*2
Hz
*1
50.0/60.0
V
*1