Toshiba TOSVERT VF-AS3 Instruction Manual page 402

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 33. 2
<F669: Terminal FP switching>
<F676: Terminal FP pulse train output function>
<F677: Maximum pulse number of pulse train output>
<F678: Pulse train output filter>
■ Function
Pulse trains can be output from terminal [FP]. Set the pulse output function and the number of
4
pulses.
■ Parameter setting
4
Title
6
F669
F676
F677
F678
9
*1
For details, refer to [11. 7].
■ Setting method
For example, to output frequency (0 - 60Hz) at 0 - 600 pulse, set as follows.
<FH>= "60.0", <F669>= "1", <F676>= "0", <F677>= "0.60"
When the item selected by <F676> has reached the value of the reference of maximum value, the
number of pulse set by <F677: maximum pulse number of pulse train output> is output.
ON pulse width is a fixed width. When outputting the maximum number of pulses set by <F677>, the
width is fixed at a value, where the duty ratio is 50%.
Therefore, the duty ratio varies according to the output pulse.
For example,
• <F677>="0.80" (kpps), ON pulse width = approx. 0.6 (ms)
• <F677>="1.00" (kpps), ON pulse width = approx. 0.5 (ms)
• <F677>="1.60" (kpps), ON pulse width = approx. 0.3 (ms)
Pulses below 15pps cannot be output.
6. [Advanced] How to use parameters
Pulse train output
Parameter name
Terminal FP switching
Terminal FP pulse train
output function
Maximum pulse number
of pulse train output
Pulse train output filter
F669 : Terminal FP switching
0: Digital output
1: Pulse output
Adjustment range
0: Digital output
1: Pulse output
*1
0-149
0.50 - 30.00
1 - 1000
6-160
E6582062
STOP
0.0Hz
14:10
Unit
Default setting
0
0
kpps
8.00
ms
64