Emergency off
<F603: Emergency off stop pattern>
<F604: Emergency DC braking time>
■ Function
Set the stop pattern for emergency off
At the time of emergency off, a trip occurs. The trip display is "E".
■ Parameter setting
Title
Parameter name
F603
Emergency off stop
pattern
F604
Emergency DC braking
time
F251
DC braking current
F515
Deceleration time 4
*1
Depending on capacity. For details, refer to [11. 6].
■ Select the setting value for <F603: Emergency off stop pattern>
0: Trip
A trip occurs by emergency off command. The motor performs coast stop.
1: Trip after Deceleration stop
A trip occurs after deceleration stop is performed for the period of time set for <dEC: Deceleration
time 1>.
2: Trip after Emergency DC braking
The inverter stops after emergency DC braking, and a trip occurs.
Set <F251: DC braking current> and <F604: Emergency DC braking time>.
3: Trip after deceleration stop by <F515>
A trip occurs after deceleration stop is performed for the period of time set for <F515: Deceleration
time 4>.
Set <F515>.
F603 : Emergency off stop pattern
0: Trip
1: Trip after Deceleration stop
2: Trip after Emergency DC brake
3: Trip after dec stop by F515
4: Trip after Quick dec stop
Adjustment range
0: Trip
1: Trip after Deceleration stop
2: Trip after Emergency DC braking
3: Trip after deceleration stop by
F515
4: Trip after Quick deceleration stop
5: Trip after Dynamic quick
deceleration stop
0.0-20.0
0 - 100
0.0-6000
6-123
E6582062
STOP
0.0Hz
13:53
Unit
Default setting
0
s
1.0
%
50
s
*1