Toshiba TOSVERT VF-AS3 Instruction Manual page 592

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Trip
display
E-13
4
4
E-18
E-19
8
E-20
9
E-21
E-22
13
E-23
E-24
E-25
E-26
13. Trip information and measures
Failure
Trip name
code
002D
Abnormal
1) When <Pt: V/f Pattern> = "0" to "9", an
speed error
over speed condition occurred.
Over speed condition:
In case F623≠0.0, F624≠0.0, the
condition which estimated frequency is
not inside of "output frequency -
<F624>" to "output frequency +
<F623>" continues <F622> times.
2) When <Pt: V/f Pattern> = "10" to "11",
over speed continued by PG failure,
etc.
Over speed condition:
In case F623≠0.0, F624≠0.0, the
condition which measured frequency is
not inside of "output frequency -
<F624>" to "output frequency +
<F623>" continues <F622> times.
3) Due to overvoltage limit operation, the
output frequency exceeded
<FH: Maximum frequency>
+12 Hz or <FH> + <vL: Base frequency
1> x 0.1.
0032
Analog input
The input level of the terminal [II] became
disconnecting
the setting value or less of <F633: II
*
analog input disconnection detection
level>
0033
CPU
Communication error between control
communicatio
CPU.
n error
0034
Over torque
• The setting value of the <F402: Auto-
boost
matic torque boost> is very high.
• Impedance on the motor is low.
0035
CPU1 fault B
Control CPU fault.
0036
Embedded
Fault in the embedded Ethernet.
Ethernet fault
0037
Option fault
Fault in the option connected to slot A.
(slot A)
0038
Option fault
Fault in the option connected to slot B.
(slot B)
0039
Option fault
Fault in option 3.
(slot C)
003A
CPU2 fault
Control CPU fault.
*Enable/Disable can be selected for trip with a parameter.
Detection factor
1) 3)
• Check whether a problem exists in input
• When the regenerative energy is large,
2) Check the PG wiring and setting.
• Check that the signal line connected to
• Check if the <F633> setting is correct.
Turn off the power and then turn it on
again.
If the error occurs again, contact your
Toshiba distributor.
Set the motor parameters according to the
motor characteristic, and perform auto-
tuning.
<vL: Base frequency 1>,
<vLv: Base frequency voltage>,
<F405: Motor rated capacity>,
<F415: Motor rated current>,
<F417: Motor rated speed>,
<F400: Offline auto-tuning>, etc.
Fault in internal inverter.
Contact your Toshiba distributor.
Fault in internal inverter.
Contact your Toshiba distributor.
Fault in the option.
Contact your Toshiba distributor.
Fault in the option.
Contact your Toshiba distributor.
Fault in the option.
Contact your Toshiba distributor.
Fault in internal inverter.
Contact your Toshiba distributor.
13-2
E6582062
Measures
voltage.
install a braking resistor (option).
the terminal [II] is not disconnected.