6. 2. 4
Selecting input signals of the optional terminals
[AI4] and [AI5]
<F148: Terminal AI4 input select>
<F149: Terminal AI5 input select>
■ Function
These parameters select an input signal for the optional terminals [AI4] and [AI5].
■ Parameter setting
Title
Parameter name
F148
Terminal AI4 input select
F149
Terminal AI5 input select
• How to operate the operation panel -> Refer to [3. 1. 1].
Reference
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3].
F148 : AI4 input select
1: Voltage input (0-10V)
2: Voltage input (-10 to +10V)
3: Current input (0-20mA)
4: PTC input
5: PT100(2-wire)input
Adjustment range
1: Voltage input (0-10 V)
2: Voltage input (-10 to +10 V)
3: Current input (0-20 mA)
4: PTC input
5: PT100 (2-wire) input
6: PT100 (3-wire) input
7: PT1000 (2-wire) input
8: PT1000 (3-wire) input
9: KTY84 input
6-11
E6582062
STOP
0.0Hz
12:46
Default setting
1
1
6. [Advanced] How to use parameters
3
4
6
9