Toshiba TOSVERT VF-AS3 Instruction Manual page 446

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

7. 2. 2
Signals are output to external equipment from the inverter.
You can select the functions for the digital output terminals and the relay logic output terminals from a
variety of output terminal functions.
Two types of functions can be set for the terminals [FP] and [R1A]-[R1C]. In this case, output is possible
when the two functions are simultaneously turned ON or either of the functions is turned ON.
■ Configuration of the control terminal block
4
4
4
7
■ Use conditions
9
7. Operating using external signals
Setting the functions to the output terminals
(for sink logic)
Functions of the terminals
[FLA]-[FLB]-[FLC]:
Set in parameter <F132> *1
Functions of the terminals [R1A]-[R1C],
[R2A]-[R2C]:
Set in parameter <F130>, <F137> *1
Functions of the terminal [FP]:
Set in parameter <F131>, <F138> *1
FLA
FLB
FL
FLC
R1A
R1C
R2A
R2C
*1
With relay contact output, chattering (momentary
ON/OFF of contact) is generated by external
FP
factors of the vibration and the impact, etc. In
particular, please set a filter of 10 ms or more, or
timer for measures when connecting it directly to
CC
the input unit of the programmable controller.
When connecting the programmable controller,
use the terminal [FP] if possible.
7-8
E6582062